FR Series Fans - Specifications


 

Dimensional Data
Model *A1 A2 C D E F
FR 100 4 5 9 1/2 6 1/8 7/8 7/8
FR 110 4 5 9 1/2 6 1/8 7/8 7/8
FR 125 - 5 9 1/2 6 1/8 7/8 -
FR 140 6 6 1/4 11 3/4 5 7/8 1 7/8
FR 150 6 6 1/4 11 3/4 5 7/8 1 7/8
FR 160 6 6 1/4 11 3/4 6 3/8 1 7/8
FR 200 8 10 13 1/4 6 1/4 1 1/2 1 1/2
FR 225 8 10 13 1/4 6 1/4 1 1/2 1 1/2
FR 250 - 10 13 1/4 6 1/4 1 1/2 -

All dimensions in inches.
*) Duct connections are
1/8" smaller than duct size.


Air Performance Graphs


Performance Data
Fan
Model
Energy
Star
RPM Volts Rated
Watts
Wattage
Range
Max.
Amps
0" .2" .4" .6" .8" 1.0" 1.5" Max.
Ps
Duct
Dia.
FR 100 V 2900 115 19 13-19 0.18 122 100 78 55 15 - - 0.87" 4"
FR 110 - 2900 115 80 62-80 0.72 167 150 133 113 88 63 4 1.60" 4"
FR 125 V 2950 115 18 15-18 0.18 148 120 88 47 - - - 0.79" 5"
FR 140 V 2850 115 61 47-62 0.53 214 190 162 132 99 46 - 1.15" 6"
FR 150 V 2700 115 71 54-72 0.67 263 230 198 167 136 106 17 1.58" 6"
FR 160 - 2750 115 129 103-130 1.14 289 260 233 206 179 154 89 2.32" 6"
FR 200 V 2750 115 122 106-128 1.11 408 360 308 259 213 173 72 2.14" 8"
FR 225 V 3100 115 137 111-152 1.35 429 400 366 332 297 260 168 2.48" 8"
FR 250 - 2850 115 241 146-248 2.40 649 600 553 506 454 403 294 2.58" 10"

FR Series performance is shown with ducted outlet. Per HVI's Certified Ratings Program, charted air been derated by a factor based on actual test results and the certified rate at .2 inches WG.

=
Static Pressure in Inches W.G.

 

Return to Fantech Inline Duct Fan