FR
Series Fans - Specifications
|
Model |
*A1 |
A2 |
C |
D |
E |
F |
|
FR 100 |
4 |
5 |
9 1/2 |
6 1/8 |
7/8 |
7/8 |
|
FR 110 |
4 |
5 |
9 1/2 |
6 1/8 |
7/8 |
7/8 |
|
FR 125 |
- |
5 |
9 1/2 |
6 1/8 |
7/8 |
- |
|
FR 140 |
6 |
6 1/4 |
11 3/4 |
5 7/8 |
1 |
7/8 |
|
FR 150 |
6 |
6 1/4 |
11 3/4 |
5 7/8 |
1 |
7/8 |
|
FR 160 |
6 |
6 1/4 |
11 3/4 |
6 3/8 |
1 |
7/8 |
|
FR 200 |
8 |
10 |
13 1/4 |
6 1/4 |
1 1/2 |
1 1/2 |
|
FR 225 |
8 |
10 |
13 1/4 |
6 1/4 |
1 1/2 |
1 1/2 |
|
FR 250 |
- |
10 |
13 1/4 |
6 1/4 |
1 1/2 |
- |
|
All dimensions in
inches.
*) Duct connections are
1/8" smaller than duct size.
 |


Fan
Model |
Energy
Star |
RPM |
Volts |
Rated
Watts |
Wattage
Range |
Max.
Amps |
0" |
.2" |
.4" |
.6" |
.8" |
1.0" |
1.5" |
Max.
Ps |
Duct
Dia. |
|
FR 100 |
V |
2900 |
115 |
19 |
13-19 |
0.18 |
122 |
100 |
78 |
55 |
15 |
- |
- |
0.87" |
4" |
|
FR 110 |
- |
2900 |
115 |
80 |
62-80 |
0.72 |
167 |
150 |
133 |
113 |
88 |
63 |
4 |
1.60" |
4" |
|
FR 125 |
V |
2950 |
115 |
18 |
15-18 |
0.18 |
148 |
120 |
88 |
47 |
- |
- |
- |
0.79" |
5" |
|
FR 140 |
V |
2850 |
115 |
61 |
47-62 |
0.53 |
214 |
190 |
162 |
132 |
99 |
46 |
- |
1.15" |
6" |
|
FR 150 |
V |
2700 |
115 |
71 |
54-72 |
0.67 |
263 |
230 |
198 |
167 |
136 |
106 |
17 |
1.58" |
6" |
|
FR 160 |
- |
2750 |
115 |
129 |
103-130 |
1.14 |
289 |
260 |
233 |
206 |
179 |
154 |
89 |
2.32" |
6" |
|
FR 200 |
V |
2750 |
115 |
122 |
106-128 |
1.11 |
408 |
360 |
308 |
259 |
213 |
173 |
72 |
2.14" |
8" |
|
FR 225 |
V |
3100 |
115 |
137 |
111-152 |
1.35 |
429 |
400 |
366 |
332 |
297 |
260 |
168 |
2.48" |
8" |
|
FR 250 |
- |
2850 |
115 |
241 |
146-248 |
2.40 |
649 |
600 |
553 |
506 |
454 |
403 |
294 |
2.58" |
10" |
FR Series
performance is shown with ducted outlet. Per HVI's Certified Ratings
Program, charted air been derated by a factor based on actual test
results and the certified rate at .2 inches WG.
|
|
Static
Pressure in Inches W.G. |
|